• VK
  • DZEN
  • INSTAGRAM
445009, Samara region, mountains. Tolyatti st.
Novozavodskaya 2a, building 309

SPOT DETECTOR IP212-116 TRION

SPOT DETECTOR IP212-116 TRION
Price: 11 920 RUB
Type of protection:
  • VZ (0ExiaIIBT6Ga)
  • MK (1ExdIIBT6Gb)
You choosed:

    The detector is designed to detect fires accompanied by smoke or low-concentration combustion products in enclosed spaces of various buildings and structures, and to send a "Fire" alert to the control panel. The detector can be installed in explosion-hazardous areas of indoor and outdoor installations of class 0 and lower, depending on the design.

    Review of the TRION VZ detector

    Review of the TRION MK detector

    Name IP 212-116.2 Trion MK IP 212-116 Trion VZ
    Explosion protection marking 1Ex d ia IIB T6 Gb 0Ex ia IIB T6 Ga
    Marking of spark protection parameters   LI: 10μH, CI: 1000pF,
    Ui: 30B, Ii: 20mA, PI: 0.3W
    Degree of protection of the shell IP67/IP31 IP67/IP31
    Operating temperature range -40°С .. +75°С -40°С .. +75°С
    Supply voltage range 10V .. 30V 10V .. 30V
    Current consumption:    
    in standby mode, no more 90 µA 90 µA
    in alarm mode, no more 20 mA 100 mA
    Detector sensitivity 0.05 dB/m .. 0.2 dB/m 0.05 dB/m .. 0.2 dB/m
    Detector response time, no more than 5 sec. 5 sec.
    Body material

    Aluminum alloy,
    Stainless steel

    Impact-resistant polyamide

    Table for selecting the ratings of additional resistors

    Type of control panel Connection parameters
    Parallel connection (for short circuit) Sequential connection (on opening)
    LB-07 Rд must provide current consumption >15 mA, Rd = 11 kOhm, Rok = 2 kOhm, VDok = KD522.
    Rok = 2 kOhm, VDok = KD522.
    Beam Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A. Rd = 2.2 kOhm, Rok = 2.4 kOhm, VDok = KD521A.
    PPK-2 Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A. Rd = 10.0 kOhm, Rok = 3.6 kOhm, VDok = KD521A.
    Bolide Rд = 1.5 kOhm (3.0 kOhm - to determine double operation), Rд = 8.2 kOhm (4.7 kOhm - to determine double operation),
    Rок = 4.7 kOhm, VDок do not install Rок = 4.7 kOhm, VDок do not install
    Yakhont-16i Rд = 1.8 kOhm (4.0 kOhm - to determine double operation), Not applicable
    Rок = 8.2 kOhm, VDок do not install
    VERS Rд = 820 Ohm (1.8 kOhm - to determine double operation), Rд = 10 kOhm (4.7 kOhm - to determine double operation),
    Rок = 7.5 kOhm, VDок do not install Rок = 7.5 kOhm. Do not install VDок.

    AM – indicates the presence of a product modification with an address mark.

    • The IP 212 Trion is a maximum-range detector and can be used in short-circuit alarm loops (parallel connection). The "Fire" alarm is provided by a sudden decrease in the detector's resistance.
    • The detector has a built-in optical indication of operation.
    • A replaceable current-limiting resistor is used for configuration of the fire alarm control panel type. The detector's trigger signal remains active after exposure to combustion products ceases. The detector can be returned to standby mode from the control panel.
    • The IP 212 Trion VZ detector is supplied with two cable entries, which allow the detector to be installed in an alarm circuit with a round cable with a diameter of 6-10 mm.
    • The IP 212 Trion MK detector is supplied with cable entries of various designs:
      • for open installation of connected cable with a diameter of 6-12 mm (index in the designation - K );
      • for laying the connecting cable in a G1/2 pipe ( TG-1/2 );
      • for laying the connecting cable in a G3/4 ( TG-3/4 ) pipe;
      • for connecting armoured cable with a diameter of 6-12 mm ( B).