The detector is designed to detect fires accompanied by smoke or low-concentration combustion products in enclosed spaces of various buildings and structures, and to send a "Fire" alert to the control panel. The detector can be installed in explosion-hazardous areas of indoor and outdoor installations of class 0 and lower, depending on the design.
| Name | IP 212-116.2 Trion MK | IP 212-116 Trion VZ |
| Explosion protection marking | 1Ex d ia IIB T6 Gb | 0Ex ia IIB T6 Ga |
| Marking of spark protection parameters | LI: 10μH, CI: 1000pF, | |
| Ui: 30B, Ii: 20mA, PI: 0.3W | ||
| Degree of protection of the shell | IP67/IP31 | IP67/IP31 |
| Operating temperature range | -40°С .. +75°С | -40°С .. +75°С |
| Supply voltage range | 10V .. 30V | 10V .. 30V |
| Current consumption: | ||
| in standby mode, no more | 90 µA | 90 µA |
| in alarm mode, no more | 20 mA | 100 mA |
| Detector sensitivity | 0.05 dB/m .. 0.2 dB/m | 0.05 dB/m .. 0.2 dB/m |
| Detector response time, no more than | 5 sec. | 5 sec. |
| Body material |
Aluminum alloy, |
Impact-resistant polyamide |
Table for selecting the ratings of additional resistors
| Type of control panel | Connection parameters | |
| Parallel connection (for short circuit) | Sequential connection (on opening) | |
| LB-07 | Rд must provide current consumption >15 mA, | Rd = 11 kOhm, Rok = 2 kOhm, VDok = KD522. |
| Rok = 2 kOhm, VDok = KD522. | ||
| Beam | Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A. | Rd = 2.2 kOhm, Rok = 2.4 kOhm, VDok = KD521A. |
| PPK-2 | Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A. | Rd = 10.0 kOhm, Rok = 3.6 kOhm, VDok = KD521A. |
| Bolide | Rд = 1.5 kOhm (3.0 kOhm - to determine double operation), | Rд = 8.2 kOhm (4.7 kOhm - to determine double operation), |
| Rок = 4.7 kOhm, VDок do not install | Rок = 4.7 kOhm, VDок do not install | |
| Yakhont-16i | Rд = 1.8 kOhm (4.0 kOhm - to determine double operation), | Not applicable |
| Rок = 8.2 kOhm, VDок do not install | ||
| VERS | Rд = 820 Ohm (1.8 kOhm - to determine double operation), | Rд = 10 kOhm (4.7 kOhm - to determine double operation), |
| Rок = 7.5 kOhm, VDок do not install | Rок = 7.5 kOhm. Do not install VDок. | |
AM – indicates the presence of a product modification with an address mark.