The IP 212/101-116.4-A1 Redut MK explosion-proof, optical-electronic, point-type smoke and heat fire alarm is designed for installation in locations where the onset and progression of a fire (primary smoke or temperature rise) cannot be reliably predicted. Dust compensation in the smoke chamber maintains the alarm's sensitivity at the set level and eliminates false alarms, significantly extending the operating time between maintenance. The alarm complies with TR CU 012/2011, TR EAEU 043/2017, and GOST R 53325-2012.
The detectors are designed for operation at ambient temperatures from minus 40°C to plus 75°C, climatic version UHL category 2, relative air humidity of 93% at a temperature of no more than 400C. Atmospheric pressure from 84 to 106.7 kPa. Seals and connections of the detector housing structural elements ensure a protection rating according to GOST 14254-2015 (IEC 60529:2013) "Degree of protection provided by enclosures (IP Code)" of the switching compartment - not lower than IP67; smoke chamber - not lower than IP31.
The detector has explosion protection of the type "flameproof enclosure "d"" and "intrinsically safe electrical circuit "ib"" (external smoke detector). Depending on the category of explosive mixture IIB and IIC, the enclosure design is divided into two types in accordance with the requirements of GOST IEC 60079-1-2011. Explosion protection marking according to GOST 31610.0-2014 (IEC 60079-0:2011): 1Ex d [ib] IIB T6 Gb and 1Ex d [ib] IIC T6 Gb. The housing material is an aluminum alloy with a total magnesium, titanium, zirconium content of no more than 7.5%.
The detector can be installed in hazardous areas of indoor and outdoor installations in accordance with the classification of GOST IEC 60079-10-1-2011 and other directives governing the use of electrical equipment in hazardous areas. The environment may contain explosive gas and vapor mixtures with air of categories IIA, IIB, and IIC.
In terms of the method of protecting a person from electric shock, the detector complies with class III according to GOST IEC 61140-2012.
The detectors comply with the standards and requirements of electromagnetic compatibility according to GOST R 53325 with test severity level 2. Radio interference from the detector does not exceed the standards established by GOST 30805.22-2013 (CISPR 22:2006) for class B equipment.
IP 212/101-116.4-A1 Redut MK is a maximum differential action detector and can be used in short-circuit alarm loops (parallel connection).
| Explosion protection marking | 1Ex d [ib] IIC T6 Gb |
| Degree of protection of the shell | IP67/IP31 |
| Operating temperature range | -40°С .. +75°С |
| Supply voltage range | from 10 to 30V |
| Current consumption: | |
| in standby mode, no more | no more than 0.25 mA |
| in alarm mode, no more | no more than 20 mA±3% or 5 mA±1% |
| Detector sensitivity | |
| smoke detector alarm | not less than 0.05 and not more than 0.2 dB/m |
| thermal at ambient temperature (54…65) °C and more | corresponds to class A1, clause 4.5.1.2 of GOST 53325, table 4.1 |
| Detector response time, no more than | 10 sec |
| The value of electrical insulation resistance | not less than 20 MOhm |
| The value of electrical strength of insulation | not less than 0.75 kV |
| Mean time between failures in standby mode | at least 60,000 hours |
| Average service life | at least 10 years |
| Weight | |
| aluminum alloy | no more than 1.6 kg |
| stainless steel | no more than 4.7 kg |
| Overall dimensions without cable entries | 150x146x105mm |
Operating modes of the built-in indicator.
Table 1.
| Opening hours | Indication | State |
| Fire | continuous glow | Detector activation |
| Duty | Intermittent glow with a period of 4 seconds. | Normal operation |
| Dustiness | Double flashes with a period of 1 sec. | It is functional, but requires maintenance: clean the camera |
Example of detector designation when ordering:
center;" width="30"> X 7
| IP | X 1 X 2 X 3 | X 3 | – 116.4 – | X 4 | Redoubt | X 5 | X 6 | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
1) IP – fire alarm;
2) Controlled fire factor:
- 1 – heat detector (indicated for a combined detector);
- 2 – smoke detector.
3) Operating principle:
- 01 – using the dependence of the electrical resistance of elements on temperature;
- 12 – optical-electronic; - designation of the combined detector - 212/101.
4) Development serial number – 116.4.
5) Response temperature (54 0 C - 65 0 C) – A1. Specified for a combined detector;
6) Name of the detector:
- Redut is the name of the detector.
7) Type of explosion protection:
- MK - explosion-proof enclosure "d".
8) Body material:
- A - aluminum alloy is installed by default and is not specified in the designation;
- H - stainless steel.
9) Cable entry type:
- K – for open installation of cables with a diameter of 6.5-13.9 mm;
- 1/2TV – for laying a cable with a diameter of 6.5-13.9 mm in a pipe with a connecting internal thread G1/2;
- 1/2ТН – for laying cable with a diameter of 6.5-13.9 mm in a pipe with a connecting external thread G1/2;
- B – for laying armoured cable with an inner sheath diameter of 6.5-13.9 mm;
- B2 – for laying with double sealing of armoured cable with an outer part with a diameter of 12.5-20.9 mm and an inner sheath diameter of 6.5-13.9 mm;
- KM10 – for laying cable with a diameter of 3.1-8.6 mm in a metal sleeve RZTsKh-10;
- KM12 – for laying cable with a diameter of 3.1-8.6 mm in a metal sleeve RZTsKh-12;
- KM15 – for laying cable with a diameter of 6.1-11.7 mm in a metal sleeve RZTsKh-15;
- KM20 – for laying cable with a diameter of 6.5-13.9 mm in a metal sleeve RZTSKH-20.