Degree of protection against dust and moisture penetration according to GOST 14254 - IP66/IP67.
General-purpose industrial junction boxes KVOP-N-XXX…X and KVOP-P-XXX…X can be equipped with drainage devices, plugs, and cable entries of various designs. Cable entries have metric (M) threads, with thread sizes M16x1.5, M20x1.5, M25x1.5, M32x1.5, M40x1.5, and M50x1.5. The maximum quantity depends on the enclosure dimensions.
Equipment entries are installed with a convenient wrench head positioning in accordance with GOST 13682-80. Cable entries allow for the input and output of round cables of various diameters:
The type, quantity, and location of cable entries are specified when ordering. Each cable entry includes rubber cable seals.
These boxes are designed to connect (branch) general-purpose and special-purpose electrical circuits (power, control, signaling, etc.). They are used to enter armored and unarmored round electrical cables and cables in metal sleeves.
The material used for the production of boxes is corrosion-resistant stainless steel 12X18H10T.
The boxes are designed for operation at ambient temperatures ranging from minus 60°C to plus 80°C…130°C. The operating temperature is determined by the equipment installed in the box. Climate class UHL1 according to GOST 15150, atmosphere type II according to GOST 15150. Altitude above sea level: no more than 4,300 m.
These boxes are designed to connect (branch) general-purpose and special-purpose electrical circuits (power, control, signaling, etc.). They are used to enter armored and unarmored round or flat electrical cables, as well as cables in metal sleeves.
The material used to make the boxes is polyamide.
The boxes are designed for operation at ambient temperatures ranging from minus 60°C to plus 80°C…95°C. The operating temperature is determined based on the equipment installed in the box. Climate class UHL1 according to GOST 15150, atmosphere type II according to GOST 15150. Altitude above sea level: no more than 4,300 m.
| KVOP-P | KVOP-N | |
| Body material | Polyamide | Corrosion-resistant stainless steel 12X18H10T |
| Degree of protection of the shell according to GOST 14254-2015 | IP66/IP67 | |
| Climatic performance | UHL1 | |
| Maximum permissible temperature environment under operating conditions |
from -60°C to +80°C …..+95°C (maximum temperature depends on equipment installed in the box) |
from -60°C to +80°C …..+130°C (maximum temperature depends on equipment installed in the box) |
| Overall dimensions of the case, mm | 100x100x50mm – code in the designation 101004 100x100x81mm – code in the designation 101009 122x119.5x92mm – code in the designation 121209 122x219x92mm – code in the designation 122209 158x158x91mm – code in the designation 161609 |
100 x 100 x 91 mm – code in the designation 101009 100 x 160 x 91 mm – code in the designation 101609 120 x 122 x 91 mm – code in the designation 121209 120 x 360 x 91 mm – code in the designation 123609 160 x 160 x 110 mm – code in the designation 161611 160 x 210 x 110 mm – code in the designation 162111 120 x 220 x 110 mm – code in the designation 122211 180 x 180 x 110 mm – code in the designation 181811 160 x 260 x 110 mm – code in the designation 162611 160 x 360 x 120 mm – code in the designation 163612 230 x 200 x 120 mm – code in the designation 232012 230 x 200 x 200 mm – code in the designation 232020 230 x 280 x 120 mm – code in the designation 232812 230 x 330 x 200 mm – code in the designation 233320 403 x 313 x 120 mm – code in the designation 403112 403 x 313 x 200 mm – code in the designation 403120 |
| Switching current, A - alternating current - direct current |
no more than 800 no more than 800 |
|
| Switching voltage, V - alternating current - direct current |
no more than 1000 no more than 1000 |
|
Conventional designation of the name applied to the marking plate:
| KVOP | – Y – | XXX…X | A(nx1, nx2, … nx5)–B(x)–C(nx1, nx2, … nx5)–D(x) | nts–PEnts |
| 1 | 2 | 3 | 4 | 5 |