CONTROL POSTS SERIES PKV MK 2.3 Exd

CONTROL POSTS SERIES PKV MK 2.3 Exd
Price on request
No data
You choosed:

    Explosion-proof control stations, models: PKV MK 2.3 Exd-A-ХХХ… Х, PKV MK 2.3 Exd-Н-ХХХ… Х, are designed for switching, control and indication of operating modes of electrical circuits of alternating and direct current of industrial frequency in explosive areas, and also for connecting armored and unarmored electrical cables of round or flat section in a metal hose or pipe.

    The material used for the manufacture of control posts is aluminum alloy or stainless steel 12X18H10T.

    Control stations are provided with the following types of explosion protection: GOST IEC 60079-1-2013 "explosion-proof enclosures "d"" and GOST IEC 60079-31-2013 equipment with protection against dust ignition by enclosures "t".

    The equipment belongs to electrical equipment of groups I, II and III according to GOST 31610.0-2014 and is intended for use in explosive areas of premises and outdoor installations in accordance with the explosion protection marking.The equipment can be used in explosive zones of class 0, 1 and 2 according to GOST IEC 60079-10-1-2011, as well as in mines and mines GOST 31439-2011 (EN 1710:2005).The environment may contain explosive mixtures of gases and vapors with air of category IIA, IIB, IIC, dust IIIC.

    Series control posts - PKV,
    model range: PKV MK 1.0 Exd-A-ХХХ… X, PKV MK 1.0 Exd-Н-ХХХ… X.
    Group marking for stainless steel
    electrical equipment I and III
    PB Ex db I Mb X / Ex tb IIIС T80°C… T190°C Db X
    Marking for stainless steel and aluminum
    alloy
    for electrical equipment group II and III
    1Ex db IIC T6… T3 Gb X / Ex tb IIIС T80°C… T190°C Db X
    Housing material stainless steel
    Aluminium alloy
    Housing material for mine design stainless steel
    Type of flameproof connection cylindrical connection
    Internal volume, cm 3 over 2000
    The degree of protection of the shell in accordance with GOST 14254-2015 IP66
    Ambient temperature in operation T6 - from -60°C to +80°C
    T5 - from -60°C to +95°C
    Т4 – from -60°C to +130°C
    Т3 - from -60°C to +180°C
    Temperature class according to GOST 31610.0-2014. T6, T5, T4, T3
    Climatic performance HL (F), UHL (NF), OM (MU)
    Switched current, A
    - alternating current
    - direct current

    no more than 800
    no more than 800
    Switched voltage, V
    - alternating current
    - direct current

    no more than 1000
    no more than 1000
    Model Overall dimensions without cable glands and
    external components
    Interior space by mounting plate Installation dimensions
    Aluminium alloy
    PKV MK 2.3 Exd-A-121211 120x120x107 mm 94x94x69 mm 100x145 mm
    PKV MK 2.3 Exd-A-151512 151x151x113 mm 124x124x78 mm 126x174 mm
    PKV MK 2.3 Exd-A-171713 175x175x120 mm 146x146x85 mm 150x195 mm
    PKV MK 2.3 Exd-A-232316 235x235x146 mm 203x203x106 mm 196x267 mm
    PKV MK 2.3 Exd-A-272722 277x277x195 mm 248x248x152 mm 236x316 mm
    PKV MK 2.3 Exd-A-434329 430x430x235 mm 395x395x182 mm 390x480 mm
    Stainless steel
    PKV MK 2.3 Exd-N-171713 175x175x120 mm 146x146x85 mm 150x195 mm
    PKV MK 2.3 Exd-N-232316 235x235x146 mm 203x203x106 mm 196x267 mm
    PKV MK 2.3 Exd-N-272722 277x277x195 mm 248x248x152 mm 236x316 mm
    PKV MK 2.3 Exd-N-434329 430x430x235 mm 395x395x182 mm 390x480 mm