Linear fire smoke detector IP212 Trion-L2 MK (detector) is designed to detect combustion products (smoke) in fire protection systems of explosive objects and generate a "Fire" signal.
IP212 Trion-L2 MK by the principle of operation is a threshold linear two-position optical-electronic smoke detector.Installed in large rooms with high ceilings.Recommended for use in unheated rooms.
| Explosion protection marking | 1Ex d IIB T6 Gb |
| Degree of protection of the shell | IP67 |
| Operating ambient temperature range | -40C<Ta<+50C |
| Operating range | 8-70 m |
| Controlled area | Up to 900 m2 |
| Supply voltage | 8-28 V |
| Current consumption at supply voltage of 12V: | |
| emitter block (without heating / with heating) | 25 mA / 50 mA |
| receiver unit (without heating / with heating) | 20 mA / 40 mA |
| Readiness time after switching on, no more than | 15 sec |
| Parameters of opto-coupler relays "Fire", "Fault": | |
| switching current, no more than | 100 mA |
| switching voltage, no more than | 100 V |
| closed key resistance, not less than | 15 mOhm |
| open key resistance, no more than | 16 Ohm |
| galvanic isolation voltage, not less than | 1500 V |
| Body material | Aluminum alloy, Stainless steel |
| Overall dimensions: | |
| receiver unit, emitter unit | 356x200x100 mm |
| switching blocks without inputs | D150x69.5 mm |
AM – indicates the presence of a product modification with an address mark.
Peculiarities:
The detector consists of an infrared emitter and receiver. Both the emitter and receiver are supplied with a permanently attached cable, which connects to the corresponding switching unit. The "Fire" and "Fault" relay contacts are galvanically isolated from each other and from the power line. The detectors are connected to the alarm circuit via a short circuit (in parallel). The receiver is connected via a four-wire connection with a separate power line.
The detector is supplied with cable entries of various designs:
The cable entry connection thread is G1/2. Round cables with a diameter of 8-12 mm can be inserted into the junction box.
______________________________________________
Example of detector designation when ordering:
| IP212 Trion-L2 MK | - T-1/2 |
| 1 | 2 |