The detector complies with the requirements of TU 26.30.50-208-81888935-2017 and is designed to detect combustion products (smoke) in fire protection systems of explosive objects and generate “Fire” and “Fault” signals.
The detector according to the principle of operation is a smoke threshold linear optoelectronic. To control a possible smoke zone, an infrared beam is used between the emitter and the photodetector. It is installed in large rooms with high ceilings. Recommended for use in unheated rooms.
The detectors are designed for operation at an ambient temperature from minus 40°C to plus 55°C, climatic version UHL1 according to GOST 15150-69. Atmospheric pressure from 84 to 106.7 kPa. The degree of protection of the shell is IP67 according to GOST 14254-96.
The detector corresponds to the III class of protection against electric shock according to GOST 2.2.007.0-75. The metal case has protective grounding and working insulation from current-carrying parts.
The design of the detector ensures its fire safety in accordance with GOST R 53325-2012.
The detectors are produced with housings made of stainless steel 12X18H10T and in versions that differ in the presence of an address label (Table 1).
Table 1
Name | Housing material | Connection |
IO209 Mirax-L2 MK OP N | Stainless steel 12X18H10T | Optorelay |
IO209 Mirax-L2 MK OP N-AM | Address mark |
Window material - polycarbonate 8mm thick.
External connections are made in the switching unit, which is supplied with the following types of cable glands of the KV, KV series TU 27.33.13-359-81888935-2019 (Company SMD LLC; certificate of conformity TS RU C-RU.VN02.V.00391/20 ) appendix A (fig. A). Connecting thread of cable glands M20x1.5:
Degree of protection of the shell | IP67 |
Ambient operating temperature range | -40C<Ta<+55C |
Working range | 8-70 m |
Controlled area | Up to 600 m2 |
Supply voltage | 8-28V |
Current consumption of the detector at a supply voltage of 12V: (without heating / with heating) | 20 mA / 60 mA |
Ready time after switching on, no more | 15 sec |
IR wavelength | 920 nm |
Radiation power, no more | 35 mW |
Maximum value of background illumination, not less than | 12000 lx |
Parameters of optocoupler relays "Fire", "Fault": switching current, not more than switching voltage, not more than closed key resistance, not less than public key resistance, not more than galvanic isolation voltage, not less than | 100mA 100V 15MΩ 30Ω 1500V |
Overall dimensions: emitter unit (receiver) junction box without inputs | 360x200x100 mm D150x70 mm |
Housing material | stainless steel |
Weight of the set (emitter, receiver, boxes), not more than | 6 kg |
Record designation when ordering:
IP212 TRION-L2 MK OP | H | [C, T1/2, T3/4, B, KM10, KM12, KM15, KM20] | AM |
1 | 2 | 3 | 4 |