The detector is used to detect a source of fire and transmit a signal to the control panel and is designed to work as part of automatic fire extinguishing and fire alarm systems.
The detector is a detector of maximum action and can be used in alarm loops for short circuit (parallel connection). The response temperature is set using a resistor. The current during operation (in the "FIRE" mode) is set by a resistor. The detector complies with TR CU 043/2017, GOST R 53325-2012
The detectors are produced in two versions: detectors IP 101 - 201.6 - A3 - AZIMUT MK-OP - N, IP 101 - 201.7 - C - AZIMUT MK-OP - N, IP 101 - 201.8 - D - AZIMUT MK-OP - N do not have address expander, and detectors IP 101 - 201.9 - A3 - AZIMUT MK-OP-AM - N, IP 101 - 201.10 - C - AZIMUT MK-OP-AM - N, IP 101 - 201.11 - D - AZIMUT MK-OP-AM – N is produced with address expander "S2000-AP1 version 2" manufactured by LLC "Bolid". The address version of the detector is used with the two-wire communication line controller "S2000-KDL" or "S2000-KDL-2I" as part of the integrated security system "Orion". https://bolid.ru/
The detectors can be equipped with a terminal element, which serves to monitor the state of the loop. Commercial name of the terminal element OE-N. The last character in the name indicates the body material: H - stainless steel.
Protection against electric shock according to GOST 12.2.007.0: class III.
The detector is equipped with two cable glands of the KV, KV series TU 27.33.13-359-81888935-2019. Connecting thread of cable glands M20x1.5. Cable glands allow you to enter and exit round cables of various diameters:
Degree of protection of the shell | IP67 |
Operating temperature range, °С | -60...+135 |
Supply voltage range, V | 6...27 |
Current consumption in standby mode at a supply voltage of 24 V | 0.35 mA |
Own current consumption in the "Fire" mode, no more | 2.3 mA. |
Ready time after supply voltage | no more than 0.5 sec. |
Overall dimensions without cable glands, mm | 113x1000x162 |
Designation when ordering:
IP 101-201.9-A3-AZIMUT MK-OP-AM - | H | – TV1/2 – | MR |
1 | 2 | 3 | 4 |
Downloads: