Manual fire detectors and remote start devices comply with the requirements of TR EAEU 043/2017, GOST R 53325-2012.
Manual fire detectors of the IP 512 HORIZONT OP-N series are manufactured in two versions with an addressable expander IP 512-451.5-A-HORIZONT OP-AM-N and without it (without an address label) IP 512-451.4-A-HORIZONT OP-N and are used to manually trigger a fire alarm.
Remote start devices of the UDP 512 HORIZONT "PUSK" OP - N series are manufactured in two versions with an address expander UDP 512 - 451.7 - V - HORIZONT "PUSK" OP-AM - N and without it (without an address label) UDP 512 -451.6 - V - HORIZONT "PUSK" OP - N and are components of a block-modular PPU, designed for manual start of fire extinguishing systems, smoke removal, etc.
UDP 512 series remote starters UDP 512 HORIZON EMERGENCY EXIT OP-N are manufactured in two versions with address expander UDP 512-451.19-A-HORIZON EMERGENCY EXIT OP-AM and without it (without address label) UDP 512-451.18 - A - HORIZON "EMERGENCY EXIT" OP - N and are components of a block-modular PPU designed to unlock emergency exits.
Equipment with an individually assigned address interacts with the S2000-AP1 version 2 address expander manufactured by Bolid LLC. The address version of the detector is used with the two-wire communication line controller "S2000-KDL" or "S2000-KDL-2I" as part of the integrated security system "Orion". https://bolid.ru/ .
Case material of IPR and UDP is corrosion-resistant stainless steel.
IPR, UDP is equipped with two cable glands of the KV, KV series TU 27.33.13-359-81888935-2019. Connecting thread of cable glands M20x1.5. Cable glands allow you to enter and exit round cables of various diameters:
General industrial manual fire detectors and remote start devices have differences in marking, because differ in purpose.
IP 512-451.4 - A - HORIZON OP - N | Manual fire detector class A (one-action activation) with addressless design |
IP 512-451.5 - A - HORIZON OP-AM - N | Manual fire detector class A (one-action activation) with addressable design |
UDP 512-451.6 - V - HORIZON "START" OP | Class B remote starter (two-action activation) with non-addressed version |
UDP 512-451.7 - V - HORIZON "START" OP-AM - N | Class B remote starter (two-action activation) with addressable version |
UDP 512-451.18 - A - HORIZON "EMERGENCY EXIT" OP - N | Class A remote starter (single-action activation) with non-addressed version |
UDP 512-451.19 - A - HORIZON "EMERGENCY EXIT" OP-AM - N | Class A remote starter (single-action activation) with addressable design |
IP 512-451.4 - A - HORIZON OP - N | UDP 512-451.6 - V - HORIZON "START" OP | UDP 512-451.18 - A - HORIZON "EMERGENCY EXIT" OP - N | |
IP 512-451.5 - A - HORIZON OP-AM - N | UDP 512-451.7 - V - HORIZON "START" OP-AM - N | UDP 512-451.19 - A - HORIZON "EMERGENCY EXIT" OP-AM - N | |
Case color | Red | Yellow | Green |
Material | Stainless steel | ||
Activation class according to GOST 53325 | A (one action) | B (two actions) | A (one action) |
Ambient temperature | -60°С … +75°С | ||
Degree of protection of the shell | IP66/67 | ||
Rated supply voltage | 12V - 24V | ||
Own current consumption, no more Non-address execution:
|
300uA
23mA | ||
Maximum allowable current in alarm mode, no more | 100mA | ||
The maximum allowable switching current on the relay contacts, no more | 2A | ||
The maximum allowable voltage on the relay contacts, no more | 250V | ||
Overall dimensions, mm, no more (* without cable glands) | 113*х109х86 |
Designation when ordering:
X 1 - | X 2 - | X 3 - | X 4 |
1 | 2 | 3 | 4 |