The detector is designed to detect fires accompanied by the appearance of smoke or combustion products of low concentration in closed rooms of various buildings and structures, and to send a "Fire" notification to the control panel. The detector can be installed in hazardous areas of premises and outdoor installations of class 0 and lower, depending on the version.
| Name | IP 212-116.2 Trion MK | IP 212-116 Trion VZ |
| Explosion protection marking | 1Ex d ia IIB T6 Gb | 0Ex ia IIB T6 Ga |
| I.S. parameter labeling | LI: 10uH, CI: 1000pF, | |
| Ui: 30V, Ii: 20mA, PI: 0.3W | ||
| Degree of protection of the shell | IP67/IP31 | IP67/IP31 |
| Operating temperature range | -40°С .. +75°С | -40°С .. +75°С |
| Supply voltage range | 10V .. 30V | 10V .. 30V |
| Consumption current: | ||
| in standby mode, no more | 90uA | 90uA |
| in alarm mode, no more | 20mA | 100mA |
| Detector sensitivity | 0.05 dB/m .. 0.2 dB/m | 0.05 dB/m .. 0.2 dB/m |
| Detector response time, no more | 5 sec. | 5 sec. |
| Housing material | Aluminium alloy, | High impact polyamide |
Selection table for additional resistors
| FACP type | Connection options | |
| Parallel connection (make) | Sequential connection (on opening) | |
| LB-07 | Rd must ensure current consumption> 15 mA, | Rd \u003d 11 kOhm, Rok \u003d 2 kOhm, VDok \u003d KD522. |
| Rok \u003d 2 kOhm, VDok \u003d KD522. | ||
| Ray | Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A. | Rd = 2.2 kOhm, Rok = 2.4 kOhm, VDok = KD521A. |
| PPK-2 | Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A. | Rd = 10.0 kOhm, Rok = 3.6 kOhm, VDok = KD521A. |
| fireball | Rd \u003d 1.5 kOhm (3.0 kOhm - to determine double drawdown), | Rd \u003d 8.2 kOhm (4.7 kOhm - to determine double drawdown), |
| Rok \u003d 4.7 kOhm, do not install VDok | Rok \u003d 4.7 kOhm, do not install VDok | |
| Yakhont-16i | Rd \u003d 1.8 kOhm (4.0 kOhm - to determine double drawdown), | Not applicable |
| Rok = 8.2 kOhm, do not set VDok | ||
| WERS | Rd \u003d 820 Ohm (1.8 kOhm - to determine double drawdown), | Rd \u003d 10 kOhm (4.7 kOhm - to determine double drawdown), |
| Rok = 7.5 kOhm, do not set VDok | Rok = 7.5 kOhm. Do not install VDoc | |
AM - indicates the presence of a product modification with an address label.