The detector is designed to detect fires accompanied by the appearance of smoke or low-concentration combustion products in enclosed spaces of various buildings and structures by detecting optical radiation reflected from smoke particles and sending a “Fire” notice to the control panel. Alarm notification "Fire" is provided by an abrupt decrease in the resistance of the detector when connected in parallel to the fire alarm loop. The detector complies with TR EAEU 043/2017, GOST R 53325-2012.
The detector is designed for operation at ambient temperature from minus 40°С to plus 75°С, climatic version UHL2 according to GOST 15150-69. The degree of protection of the enclosure is IP67/IP31 according to GOST 14254. The degree of protection IP31 refers to a smoke detector that cannot be placed inside a flameproof enclosure. Placement category 2 according to GOST 15150-69.
Case material - either corrosion-resistant stainless steel 12X18H10T.
According to the method of protecting a person from electric shock, the detector corresponds to class III according to GOST IEC 61140-2012.
The detectors comply with the norms and requirements of electromagnetic compatibility in accordance with GOST R 53325-2012 with a degree of test severity 2. Radio interference from the detector does not exceed the standards established by GOST 30805.22-2013 (CISPR 22:2006) for class B equipment.
IP 212-116.2 Trion MK-OP - N is a maximum action detector and can be used in short circuit alarm loops (parallel connection).
The detector can be manufactured with address expander "S2000-AP1 version 2" manufactured by OOO "Bolid". The address version of the detector is used with the two-wire communication line controller "S2000-KDL" or "S2000-KDL-2I" as part of the integrated security system "Orion". https://bolid.ru/
The detector is equipped with two cable glands of the KV TU 27.33.13-359-81888935-2019 series. Connecting thread of cable glands M20x1.5. Cable glands allow you to enter and exit round cables of various diameters:
Degree of protection of the shell | IP67/IP31 |
Operating temperature range | -40°С .. +75°С |
Supply voltage range | 10V .. 30V |
Consumption current: | |
in standby mode, no more | 90uA |
in alarm mode, no more | 20mA |
Detector sensitivity | 0.05 dB/m .. 0.2 dB/m |
Detector response time, no more | 5 sec. |
Housing material | Stainless steel |
FACP type | Parallel connection (make) |
LB-07 | Rd must ensure current consumption> 15 mA, |
Rok \u003d 2 kOhm, VDok \u003d KD522. | |
Ray | Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A. |
PPK-2 | Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A. |
fireball | Rd \u003d 1.5 kOhm (3.0 kOhm - to determine double drawdown), |
Rok \u003d 4.7 kOhm, do not install VDok | |
Yakhont-16i | Rd \u003d 1.8 kOhm (4.0 kOhm - to determine double drawdown), |
Rok = 8.2 kOhm, do not set VDok | |
WERS | Rd \u003d 820 Ohm (1.8 kOhm - to determine double drawdown), |
Rok = 7.5 kOhm, do not set VDok |
An example of the designation of the detector when ordering:
IP | X 1 | X 2 | 116.2 | Tryon | x3 | x4 | x5 | x6 |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |