The luminaires are intended for lighting industrial premises, warehouses, overpasses, elements of transport infrastructure, as well as for outdoor lighting and other areas where explosive gas or dust may be present, in accordance with the assigned explosion protection marking specified in the certificate of conformity TR CU 012/2011.
According to the method of application, the lamps are stationary. The luminaires have the following types of installation: pendant, wall, ceiling and cantilever.
The design of luminaires and their components is designed for reliable and safe operation under normal operation conditions.
Lamps are produced in versions that differ in body material, overall dimensions, power, and operating supply voltage. Case material and components: aluminum alloy, stainless steel, polyamide.
The luminaires comply with the general requirements of GOST 31610.0-2019 (IEC 60079-0:2017) and are provided with the following types of explosion protection: GOST IEC 60079-1-2013 “explosion-proof enclosure “d”, GOST IEC 60079-31-2013 equipment with dust ignition protection shells “t”. Marking of explosion-proof electrical equipment, operating temperature and degree of protection by enclosure according to GOST 14254-2015 (IEC 60529:2013).
The luminaires are installed in hazardous areas of class 1 and 2 according to the classification according to GOST 31610.10-1-2022 (IEC 60079-10-1:2020) and other directive documents regulating the use of electrical equipment in hazardous areas.
The luminaires belong to electrical equipment groups II and III according to GOST 31610.0-2019 (IEC 60079-0:2017) and are intended for use in explosive zones of class 1. The environment may contain explosive mixtures of gases, vapors with air IIC or IIB, dust of category IIIC.
Parameter name | Meaning | ||
Explosion protection marking according to GOST 31610.0-2019 (IEC 60079-0:2017) | 30W. | 1Ex db IIC T6 Gb X/Ex tb IIIC T80 0 C Db X | |
50W. | |||
70W. | |||
100W. | 1Ex db IIC T5 Gb X/Ex tb IIIC T95 0 C Db X | ||
Supply voltage, V | ~220… ~240 AC ~100… ~277 AC | ||
frequency Hz | 50 (60) | ||
Power, W | 30, 50, 70, 100 | ||
Luminous flux, Lm | 30W. | 3600 | |
50W. | 8400 | ||
70W. | 6100 | ||
100W. | 11200 | ||
Color temperature, K | from 2700 to 6500 default 5700 | ||
Color rendering index, Ra | ≥ 80 | ||
Temperature class | T6 / T80 0 C T5 / T95 0 C | ||
Degree of protection, IP | IP66 | ||
Operating temperature, 0 C | -20 0 С ≤ Ta ≤ +43 0 С | ||
-20 0 С ≤ Ta ≤ +58 0 С | |||
Cable connection points | M25x1.5 | ||
Terminal block | 3x1.5~4mm 2 (L+N+PE) | ||
Grounding | M5 (inner and outer ground bolts) | ||
Housing material | Aluminium alloy | ||
Dimensions, mm. | 30W, 50W. | d=175, L=313. | |
70W, 100W. | d=210, L=100. | ||
Weight, kg | 30W, 50W. | 4.5 | |
70W, 100W. | 6.8 |
ZENIT MK | - 1.1 - | YYY |
1 | 2 | 3 |
Luminous flux depending on the power of the lamps:
Lamp ZENIT MK 1.1-030
30W/3600Lm
Lamp ZENIT MK 1.1-050
50W/6100Lm
Lamp ZENIT MK 1.1-070
70W/8400Lm
Lamp ZENIT MK 1.1-100
100W/11200Lm