The detector is designed to detect fires accompanied by the appearance of electromagnetic radiation simultaneously in the ultraviolet and infrared spectral ranges and to send a "Fire" notification to the control panel.The use of the IR and UV parts of the spectrum eliminates false alarms of the detector.The detector meets the requirements of GOST R 53325-2012.The detector is used in installations for fire protection of buildings, structures, premises and equipment in open areas.
Effective for harsh climatic conditions (-60 ... + 75 C °), including the regions of the Far North (heating of the internal volume).They work with control and monitoring devices, addressable fire alarm systems, complex integrated safety management systems and automatic fire extinguishing systems of all leading Russian and foreign manufacturers.The detector meets the requirements of GOST R 53325-2012.
The list of typical production premises, technological processes, for the protection of which the product is used:
Support for the 485 Modbus protocol allows the detector to be used both in security and fire alarm systems and in automated process control systems.Connection to digital and analogue networks is possible.Diagnostics and configuration of devices can be carried out remotely for ease of maintenance at remote, low-maintenance infrastructure facilities.Registration and archiving of all events occurs automatically, the results are saved in the system.
The detectors are manufactured in versions that differ in the type of explosion protection and housing material (see.(see table 1 in the "Characteristics" tab).Explosion protection types: "flameproof enclosure" d "" and "intrinsically safe electrical circuit" ia "". Explosion protection marking, respectively: 1Ex d IIC T6 Gb X / Ex tb IIIC T85 ° C Db X and 0Ex ia IIC T6 Ga X / Ex ia IIIC T85 ° C Da X according to GOST R IEC 60079-0-2011.The "X" mark in the marking means: do not expose the light-transmitting part to mechanical stress.Body material: aluminum alloy; Cink Steel; stainless steel.
For the version "intrinsically safe electrical circuit" ia "" marking of explosion protection parameters: "Li: 1mkHn, Ci: 1000pF, Ui: 28B, Ii: 70mA, Pi: 2W" according to GOST R IEC 60079-11-2011.
The detector can be installed in hazardous areas of premises and outdoor installations according to the classification of GOST IEC 60079-10-1-2011 and other directive documents regulating the use of electrical equipment in hazardous areas.The environment may contain explosive mixtures of gases and vapors with air, categories IIA and IIB.
The detector is designed for operation at ambient temperatures from minus 60 ° С to plus 75 ° С, type of climatic modification UHL1 in accordance with GOST 15150-69.The degree of protection of the shell is IP67 in accordance with GOST 14254.Placement category 1 according to GOST 15150-69
Table 1.
Designation | Body material | Explosion protection type |
IP329 / 330-310.3-1 Telos MK-S Modbus RS485 | Cink Steel | PB Ex d I Mb X / 1Ex d IIС T6 Gb X / Ex tb IIIC T85 ° C Db X |
IP329 / 330-310.3-1 Telos MK-N Modbus RS485 | Stainless steel | PB Ex d I Mb X / 1Ex d IIС T6 Gb X / Ex tb IIIC T85 ° C Db X |
IP329 / 330-310.2-1 Telos VZ-N Modbus RS485 | Stainless steel | PO Ex ia I Ma X / 0Ex ia IIC T6 Ga X / Ex ia IIIC T85 ° C Da X |
IP329 / 330-310.3-1 Telos MK-A Modbus RS485 | Aluminium alloy | PB Ex d I Mb X / 1Ex d IIС T6 Gb X / Ex tb IIIC T85 ° C Db X |
IP329 / 330-310.2-1 Telos VZ-A Modbus RS485 | Aluminium alloy | PO Ex ia I Ma X / 0Ex ia IIC T6 Ga X / Ex ia IIIC T85 ° C Da X |
Table 2.
Characteristic | Meaning | |
Spectral sensitivity, nm | IR | 4300 |
Uv | 185 - 260 | |
Detection range of test foci, m, not less | TP-5 (N-heptane) | 25 |
TP-6 (ethyl alcohol) | 25 | |
Viewing angle, gr | IR | 90 |
Uv | 90 | |
Response time, no more, sec | ten | |
Direct light resistance, not less lux | incandescent lamps | 250 |
fluorescent lamps | 2500 | |
Resistance to optical radiation in the visible range of the spectrum, no more, lux | 80,000 | |
Supply voltage, V | 8 - 28 | |
Consumption current, no more, mA | without heating | twenty |
heated | 200 | |
Characteristics of the Sh1 and Sh2 optocoupler relays | maximum voltage, V, not more | 100 |
maximum current, mA, not more | 100 | |
open resistance, Ohm, no more | 16 | |
isolation voltage, V, not less | 1500 | |
Ready time after power supply, no more, sec | 45 | |
Diameter of the cable to be inserted, mm | 6 - 12 | |
Section of the connected conductors, mm 2 | 0.35 - 1.5 | |
Operating temperature range, С | -60 ° C .. + 75 ° C | |
Sheath protection | IP67 | |
Climatic performance | UHL1 | |
Overall dimensions, mm | 334x271x116 | |
Weight, no more, kg | 3.5kg |
An example of a detector designation when ordering:
IP330 / IP329 Telos | MK | - WITH - | Modbus RS485 - | Kv |
1 | 2 | 3 | 4 | 5 |
Downloads: