The IP101 Azimuth OP detector is used to detect the source of fire and transmit a signal to the receiving and control device and is designed to work as part of automatic fire extinguishing and fire alarm systems at special-purpose facilities.The detector has a high level of protection IP 67 in the temperature range -60C ° ... + 85C °.The detector is available in versions with a conventional (for tanks) or shortened (for rooms) thermosensitive housing part.
There are three normal values for the threshold temperature: 70 ° C; 90 ° C; 110 ° C.
Name | IP101 Azimut OP |
Sheath protection degree, IP | 67 |
Operating temperature range, ° С | -60 ... + 85 |
Supply voltage range, V | 6 ... 27 |
Consumption current at 24 V supply voltage: | - in standby mode - (0.2-0.25) mA |
- in the "fire" mode - (10.7 +/- 0.5) mA. | |
Ready time after power on | |
Overall dimensions, mm | - normal - 122x82x152 |
- extended - 122x82x259 |
The response temperature set by the manufacturer can be changed by the consumer by installing a suitable resistor in the detector terminals.The detector is equipped with resistors for setting the response temperature: 70 ° С; 90 ° C; 110 ° C.Dependence of the response temperature of the PS Azimuth OP on the resistance of the driving resistor.
T, ° C | 51 | 60 | 70 | 81 | 90 | 100 | 110 |
Rt, kΩ | thirty | twenty | 13 | 8.2 | 5.6 | 3.6 | 2.4 |
The IP101 Azimuth OP detector is supplied with two cable glands that allow the detector to be installed in an alarm loop with a round cable 6-10mm in diameter.
Downloads: