IPR 535 Horizon "Emergency exit" MK is designed to unblock emergency exits.Explosion protection marking 1Ex d IIB T6 Gb.
IPR 535 Horizon "Emergency exit" is designed to unblock emergency exits and is intended for installation in hazardous zones of class 0 and below.
Explosion protection marking | 1Ex d IIB T6 Gb |
Degree of protection of the shell | IP67 |
Operating temperature | -60C<Ta<75C |
Climatic performance | UHL1 |
Supply voltage | 8-28V |
Current consumption in standby mode, no more | 80uA |
Own current consumption in the "Fire" mode, no more | 0.7mA |
Maximum current of the external additional resistor circuit, not more than | 100mA |
Case color: | green |
Housing material | Aluminium alloy |
Dimensions without cable entries | 131x122x46mm |
FACP type | Connection options | |
Parallel connection (make) | Sequential connection (on opening) | |
LB-07 | Rd must ensure current consumption> 15 mA, | Rd \u003d 11 kOhm, Rok \u003d 2 kOhm, VDok \u003d KD522. |
Rok \u003d 2 kOhm, VDok \u003d KD522. | ||
Ray | Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A. | Rd = 2.2 kOhm, Rok = 2.4 kOhm, VDok = KD521A. |
PPK-2 | Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A. | Rd = 10.0 kOhm, Rok = 3.6 kOhm, VDok = KD521A. |
fireball | Rd \u003d 1.5 kOhm (3.0 kOhm - to determine double drawdown), | Rd \u003d 8.2 kOhm (4.7 kOhm - to determine double drawdown), |
Rok \u003d 4.7 kOhm, do not install VDok | Rok \u003d 4.7 kOhm, do not install VDok | |
Yakhont-16i | Rd \u003d 1.8 kOhm (4.0 kOhm - to determine double drawdown), | Not applicable |
Rok = 8.2 kOhm, do not set VDok | ||
WERS | Rd \u003d 820 Ohm (1.8 kOhm - to determine double drawdown), | Rd \u003d 10 kOhm (4.7 kOhm - to determine double drawdown), |
Rok = 7.5 kOhm, do not set VDok | Rok = 7.5 kOhm. Do not install VDoc |
AM - indicates the presence of a product modification with an address label.
The detector IPR535 Horizon Emergency exit MK is supplied with cable glands of various designs:
The detector IPR535 Horizon Emergency exit MK is supplied with two cable glands, which allow you to install the detector in an alarm loop with a round cable with a diameter of 6-10mm.
Files for download: