Products

Select the parameters
						УСТРОЙСТВО ДИСТАНЦИОННОГО ПУСКА <br /> УДП 512 ГОРИЗОНТ ПУСК МК
УСТРОЙСТВО ДИСТАНЦИОННОГО ПУСКА УДП 512 ГОРИЗОНТ УСТРОЙСТВО ДИСТАНЦИОННОГО ПУСКА УДП 512 ГОРИЗОНТ УСТРОЙСТВО ДИСТАНЦИОННОГО ПУСКА УДП 512 ГОРИЗОНТ УСТРОЙСТВО ДИСТАНЦИОННОГО ПУСКА УДП 512 ГОРИЗОНТ
Equipment
  • Request a price from the manager
You choosed:
  • Equipment

Explosion Proof Remote Starter Series
UDP 512 HORIZON

Explosion-proof remote start devices UDP 512 HORIZONT (UDP) are designed for manual start of a fire extinguishing system, engineering systems or unblocking emergency exits in case of fire. The detectors and UDP comply with the requirements of TR EAEU 043/2017 (GOST 53325-2012), TR CU 012/2011 (GOST 31610.0-2014).

Remote start devices belong to electrical equipment of group I, subgroup IIC and IIIC according to GOST 31610.0-2014 (IEC 60079-0) and are intended for use in explosive gas environments, including mines and mines, as well as explosive dust environments. The detector complies with the requirements of TR TS 012/2011, GOST R IEC 60079-14 and other regulatory documents governing the use of electrical equipment in hazardous areas.

UDP explosion protection marking for groups II and III in an aluminum alloy and stainless steel case - 1Ex db IIC T6 Gb / Ex tb IIIC T85°C Db (GOST IEC 60079-1-2013, GOST IEC 60079-31-2013). For groups I and III in a stainless steel case РВ Ex db I Mb / Ex tb IIIC Т85°C Db (GOST IEC 60079-1-2013, GOST IEC 60079-31-2013).

The ambient temperature for manual call points and remote starters is from minus 60°С to plus 75°С. Type of climatic version UHL (NF) and HL (F) of category 1, atmosphere type II-IV according to GOST 15150, and relative humidity of air 100% at a temperature of not more than 250C and 95% without condensation at a temperature of not more than 400C. The degree of protection of the shell is IP66/IP67 according to GOST 14254.

The principle of operation of the UDP is optoelectronic, which allows you to completely eliminate the influence of external electromagnetic fields on the operation of the detector. Devices can be installed on any surface, including ferromagnetic. The drive element is made in the form of a button.

Versions

According to the body material - UDP are made of aluminum alloy AK12OCH and stainless steel AISI 321.

According to the connection method, UDPs are produced in addressable and non-addressed versions. Connection schemes: addressable - four-wire with a separate power line; addressless - two-wire or four-wire.

In the non-address version, the "Fire" notification can be transmitted either by increasing the current of the alarm loop (two-wire circuit), or using an electromechanical relay with switched contacts (four-wire circuit with a separate power line). The "Fire" current for a two-wire connection can be set using an additional resistor during installation.

In the addressable version, a four-wire connection scheme with a separate power line is used. Compatible address systems: "S2000 Orion"; "Frontier".

UDP are compatible with almost any control and reception devices.

Explosion protection marking according to GOST R IEC 60079-0-2011A - 1Ex db IIC T6 Gb / Ex tb IIIC T85°C Db H - PB Ex db I Mb / Ex tb IIIC T85°C Db
Case colorYellow
MaterialAluminum alloy, Stainless steel
Activation class according to GOST 53325B (two actions)
Ambient temperature-60°С … +75°С
Degree of protection of the shellIP66/67
Rated supply voltage12V - 24V

Own current consumption, no more

Non-address execution:

  • in standby mode
  • in fire mode

Address execution:

  • in standby mode
  • in fire mode

 

 

300uA
1.2mA

 

23mA
20mA

Maximum allowable current in alarm mode, no more100mA
The maximum allowable switching current on the relay contacts, no more2A
The maximum allowable voltage on the relay contacts, no more250V
Housing materialAluminium alloy
stainless steel
Overall dimensions, mm, no more (* without cable glands)113*х109х86

 

Designation system when ordering

UDP 512.451.2 - A- HORIZON MK -AM -X 2 -X 3 -X 4
 1234
  1. The presence of an address label:

No label (default) – no label;

AM - the presence of an address label DPLS (address system "Orion");

  1. Case material:

No designation – aluminum alloy*;

H - stainless steel.

*Aluminum alloy is the default material and is not listed in the designation.

  1. Cable gland type:

K - for open cable laying with a diameter of 6.5-13.9 mm;

B - for an armored cable with a passage diameter of 6.5-13.9 mm (without armor);

ТН1/2 - for laying a cable with a diameter of 6.5-13.9 mm in a pipe with a connecting thread G1/2;

ТН3/4 - for laying a cable with a diameter of 6.5-13.9 mm in a pipe with a connecting thread G3/4;

KM10 - For a cable with a diameter of 3.1-8.6mm in a metal hose RZTsH-10mm;

KM12 - For a cable with a diameter of 3.1-8.6mm in a metal hose RZTsH-12mm;

KM15 - For a cable with a diameter of 6.1-11.7 mm in a metal hose RZTsH-15mm;

KM20 - For a cable with a diameter of 6.1-13.9 mm in a metal hose RZTsH-20mm;

  1. Cable entry material:

L - Nickel-plated brass (by default for an aluminum alloy detector);

H - Stainless steel (default for a stainless steel detector).

Contacts

  • SMD Company LLC
  • 445009, Samarskay obl.,
  • Togliatty,
  • st. Novozavodskaya 2a, build. 309
  • Аккредитация URS ISO 9001
Write to us, we are online!