The IP101 Azimuth MK detector is included in the alarm loop without additional current-limiting elements (there is a built-in 2kOhm resistor) and without regard to polarity.Alarm notification is provided by an increase in the current through the detector, and by turning on the indicator.
The IP101 Azimuth detector is used to detect the source of fire and transmit a signal to the receiving and control device and is designed to work as part of automatic fire extinguishing and fire alarm systems at special-purpose facilities.The detector is designed for installation in hazardous areas of class 0 and below.The detector is available in versions with a conventional (for tanks) or shortened (for rooms) thermosensitive housing part.
There are three normal values for the threshold temperature: 70 ° C; 90 ° C; 110 ° C.
Name | IP101 Azimuth MK | IP101 Azimuth |
Explosion protection marking | 1 Ex d IIB T4 Gb | 0Ex ia IIB T6 Ga |
I.S. parameter labeling | LI: 1 µH, CI: 1000 pF, UI: 27 V, II: 13 mA, PI: 0.4 W | |
Degree of protection of the shell | IP67 | IP67 |
Operating temperature range, °С | -60...+115 | -60...+85 |
Supply voltage range, V | 6...27 | 6...27 |
Current consumption in standby mode at a supply voltage of 24 V: | 0.35 mA | 0.35 mA |
Own current consumption in the "Fire" mode, no more | 2.3 mA. | 2.3 mA. |
Ready time after supply voltage | no more than 0.5 sec. | no more than 0.5 sec. |
Overall dimensions, mm | - excluding cable glands - 113x1000x162; | - regular - 122x82x152 |
- elongated - 122x82x259 |
Selection table for additional resistors
FACP type | Connection options |
Parallel connection (make) | |
LB-07 | Rd must ensure current consumption> 15 mA, |
Rok \u003d 2 kOhm, VDok \u003d KD522. | |
Ray | Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A. |
PPK-2 | Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A. |
fireball | Rd \u003d 1.5 kOhm (3.0 kOhm - to determine double drawdown), |
Rok \u003d 4.7 kOhm, do not install VDok | |
Yakhont-16i | Rd \u003d 1.8 kOhm (4.0 kOhm - to determine double drawdown), |
Rok = 8.2 kOhm, do not set VDok | |
WERS | Rd \u003d 820 Ohm (1.8 kOhm - to determine double drawdown), |
Rok = 7.5 kOhm, do not set VDok |
AM - indicates the presence of a product modification with an address label.
The response temperature set by the manufacturer can be changed by the consumer by installing an appropriate resistor in the detector terminals. The detector is equipped with resistors to set the response temperature: 70°С; 90°C; 110°C.
The dependence of the operating temperature of the IP Azimuth MK on the resistance of the setting resistor.
T, °C | 51 | 60 | 70 | 81 | 90 | 100 | 110 | 135 | 150 |
Rt, kOhm | thirty | 20 | 13 | 8.2 | 5.6 | 3.6 | 2.4 | 0.560 | 0 |
The IP101 Azimuth MK detector is supplied with cable glands of various designs:
Dependence of the operating temperature of the IP Azimuth on the resistance of the setting resistor.
T, °C | 51 | 60 | 70 | 81 | 90 | 100 | 110 |
Rt, kOhm | thirty | 20 | 13 | 8.2 | 5.6 | 3.6 | 2.4 |
The IP101 Azimuth detector is supplied with two cable glands, which allow the detector to be installed in an alarm loop with a round cable with a diameter of 6-10mm.