Explosion protection marking | PO Ex ia I Ma / 0Ex ia IIC T6 Ga X / Ex ia IIIC 850C Da X |
I.S. parameter labeling | LI: 1 µH, CI: 30 pF, UI: 27 V, II: 25 mA, PI: 0.8 W |
Degree of protection of the shell | IP67 |
Operating temperature | -60°C<Ta<70°C |
Climatic performance | |
Supply voltage | 8-28V |
Current consumption in standby mode, no more | 80uA |
Own current consumption in the "Fire" mode, no more | 0.7mA |
Maximum current of the external additional resistor circuit, not more than | 100mA |
Case color: | red |
Housing material | High impact polyamide |
Dimensions without cable entries | 134x108x46mm |
FACP type | Connection options | |
Parallel connection (make) | Sequential connection (on opening) | |
LB-07 | Rd must ensure current consumption> 15 mA, | Rd \u003d 11 kOhm, Rok \u003d 2 kOhm, VDok \u003d KD522. |
Rok \u003d 2 kOhm, VDok \u003d KD522. | ||
Ray | Rd = 2.4 kOhm, Rok = 2.4 kOhm, VDok = KD521A. | Rd = 2.2 kOhm, Rok = 2.4 kOhm, VDok = KD521A. |
PPK-2 | Rd = 1.2 kOhm, Rok = 3.6 kOhm, VDok = KD521A. | Rd = 10.0 kOhm, Rok = 3.6 kOhm, VDok = KD521A. |
Bolide | Rd \u003d 1.5 kOhm (3.0 kOhm - to determine double drawdown), | Rd \u003d 8.2 kOhm (4.7 kOhm - to determine double drawdown), |
Rok \u003d 4.7 kOhm, do not install VDok | Rok \u003d 4.7 kOhm, do not install VDok | |
Yakhont-16i | Rd \u003d 1.8 kOhm (4.0 kOhm - to determine double drawdown), | Not applicable |
Rok = 8.2 kOhm, do not set VDok | ||
WERS | Rd \u003d 820 Ohm (1.8 kOhm - to determine double drawdown), | Rd \u003d 10 kOhm (4.7 kOhm - to determine double drawdown), |
Rok = 7.5 kOhm, do not set VDok | Rok = 7.5 kOhm. Do not install VDoc |
AM - indicates the presence of a product modification with an address label.
The IPR535 detector Horizont VZ is supplied with cable glands of various designs:
The IPR535 detector Horizont VZ is supplied with two cable glands, which allow the detector to be installed in an alarm loop with a round cable with a diameter of 6-10mm.